Project

General

Profile

User story #2552

Migration of present RF PLC code from step 7 classic to TIA Portal

Added by Angela Salom 6 days ago. Updated about 3 hours ago.

Status:
New
Priority:
Normal
Assignee:
Start date:
15.04.2025
Due date:
05.05.2025
% Done:

0%

Estimated time:
16.00 h
Spent time:
Git branch (link):
Git merge to develop (link):
SVN commit (link/?p=rev):

Rfm-cs_StartMigration.zip (1.82 MB) Rfm-cs_StartMigration.zip RFM-CS Step7 classic prepared to migration of TIA PORTAL V19 Alfonso Ros, 09.04.2025 18:37
RFM-CS_V00_20250409_1834.zap19 (1.36 MB) RFM-CS_V00_20250409_1834.zap19 RFM-CS Migrated to TIA PORTAL_V19 Alfonso Ros, 09.04.2025 18:38
Report of migration PLC code to TIA PORTAL_V19.docx (308 KB) Report of migration PLC code to TIA PORTAL_V19.docx Report of migration PLC Alfonso Ros, 09.04.2025 18:42
s7_connections_before.png (20.2 KB) s7_connections_before.png Iago Dapena, 14.04.2025 12:38
s7_connections_after.png (15.1 KB) s7_connections_after.png Iago Dapena, 14.04.2025 12:38

Related issues

follows User story #2551: Check code in PLC and compare it with gitlab codeClosed08.04.202514.04.2025

History

#1 Updated by Angela Salom 6 days ago

  • follows User story #2551: Check code in PLC and compare it with gitlab code added
  • Start date changed from 08.04.2025 to 15.04.2025
  • Due date changed from 28.04.2025 to 05.05.2025

#2 Updated by Iago Dapena 6 days ago

  • Assignee changed from Iago Dapena to Angela Salom

Do we have a prefered TIA Portal version or are we free to use any of the latest releases?

Alfonso suggested to use the v20, which is the latest, but I currently do not have license for this one. I do, however, have license for v19.

#3 Updated by Alfonso Ros 5 days ago

There is no preferred version of TIA Portal. If you have a V19 license, you can use it. In the future, migrating to the next version will be very easy.

#4 Updated by Alfonso Ros 5 days ago

The PLC program has been successfully migrated from Step 7 Classic to TIA Portal V19 as part of the modernization and system standardization process. This migration facilitates future updates and ensures compatibility with newer Siemens tools and platforms.

Please find attached the following files for your review:

1.- "Rfm-cs_StartMigration.zip". This archive contains the original project in Step 7 Classic format. It has been prepared specifically for migration to TIA Portal V19, with all necessary configurations included.

2.- "RFM-CS_V0020250409_1834.zap19". This file is the migrated version of the project, now fully functional in TIA Portal V19. It includes all hardware configurations, networks, and logic converted and adapted to the new environment.

3.- Migration Report: A comprehensive document outlining the steps taken during the migration process. It includes details on the issues encountered (e.g., warning messages), the changes applied to resolve them, and any adjustments made to the program to ensure optimal performance in TIA Portal.

Alfonso Ros

#5 Updated by Alfonso Ros 4 days ago

The current internal firmware version of the CPU 317-2 PN/DP (6ES7 317-2EK14-0AB0) is version 3.2.

Before proceeding with the migration of the automation project to TIA Portal V19, it is necessary to update the CPU’s internal firmware to version 3.2.19. This firmware upgrade is a prerequisite to ensure compatibility with the features and requirements of the newer Siemens software program "TIA PORTAL".

The step-by-step procedure for performing the firmware upgrade is available on the official Siemens support website [[https://support.industry.siemens.com/cs/document/40362228/firmware-updates-for-cpu-317-2-pn-dp-(6es7317-2ek14-0ab0)?dti=0&lc=en-ES]] with Entry ID: 40362228.

A.

#6 Updated by Angela Salom about 6 hours ago

  • Assignee changed from Angela Salom to Iago Dapena

#7 Updated by Iago Dapena about 3 hours ago

Reviewing the PLC SW already migrated to TIA Portal v19 I have seen a minor error with connection names.
I have renamed them to avoid errors.